If you're working on a WELL Certification project, then you know the International WELL Building Institute (IWBI) sets requirements for how your building or workplace performs acoustically. Those requirements, along with optional features that earn points toward certification, are outlined in the WELL v2 Sound concept, which covers everything from how a floor plan is zoned and maximum noise levels to sound isolation between rooms and hearing health programs.
In this guide, we'll break down what you need to know about each of the concept's nine features, including what each one requires, how many points it's worth, and how it's verified, plus where continuous sound monitoring fits in today.
The Sound concept is one of ten concepts in WELL v2, and it sets requirements for how a building manages background noise, speech privacy, reverberation, impact noise, and hearing health. The IWBI describes its goal as supporting occupant health and well-being by identifying and addressing the acoustic factors that shape how people experience a space.
The concept has nine features: S01 is a precondition every project must meet, and S02 through S09 are optimizations that earn extra points. Together, the optimizations are worth up to 18 points, though WELL v2 counts no more than 12 points from any one concept toward certification. Points earned beyond that cap can count toward the Innovation concept instead.
|
Feature |
Type |
Max points |
What it covers |
|
S01 Sound Mapping |
Precondition |
Required |
Acoustic zoning and a design plan |
|
S02 Maximum Noise Levels |
Optimization |
3 |
Background noise limits by room type |
|
S03 Sound Barriers |
Optimization |
3 |
Sound isolation through walls and doors |
|
S04 Reverberation Time |
Optimization |
2 |
How long sound lingers in a room |
|
S05 Sound Reducing Surfaces |
Optimization |
2 |
Sound-absorbing ceilings, walls, and partitions |
|
S06 Minimum Background Sound |
Optimization |
2 |
Sound masking for speech privacy |
|
S07 Impact Noise Management (beta) |
Optimization |
3 |
Footfall and other impact noise through floors |
|
S08 Enhanced Audio Devices |
Optimization |
2 |
AV systems and audio policies |
|
S09 Hearing Health Conservation (beta) |
Optimization |
1 |
Hearing protection programs for loud work areas |
Note: S07 and S09 are beta features, so projects pursuing them also submit a feedback form that helps the IWBI refine them.
S01 requires every project to plan for acoustic problems before they happen by zoning the space and documenting a strategy to manage sound. It has two parts:
Part 1: Label Acoustic Zones. A floor plan or other design document labels each area as one of five zone types:
Where a loud zone borders a quiet zone, the project also needs a plan to either reprogram those spaces or reduce sound traveling between them. This part is verified by technical document.
Part 2: Provide an Acoustic Design Plan. Projects are required to submit a plan that outlines acoustical solutions and a timeline for putting them in place, focused on managing acoustical comfort, background noise, speech privacy, reverberation time, and/or impact noise. The plan can come from the project team or owner, or take the form of a detailed report from an acoustics professional that also describes existing conditions and measurement results. This part is verified by professional narrative.
S02 caps background noise, meaning the sound from HVAC systems, outdoor noise, and other building sources, based on how each room is used. WELL groups rooms into four categories, each with its own limits:
Each category has three limits: an average sound level (Leq) on the A-weighted scale (dBA), an average on the C-weighted scale (dBC), and a 90th percentile level (L10). The C-weighted scale includes more low-frequency sound than the A-weighted scale, and L10 is the level exceeded 10% of the time.
|
Room category |
Tier 1 (1 point) |
Tier 2 (3 points) |
|
Category 1 |
dBA: 40 dBC: 60 L10: 50 dBA |
dBA: 35 dBC: 55 L10: 45 dBA |
|
Category 2 |
dBA: 45 dBC: 65 L10: 55 dBA |
dBA: 40 dBC: 60 L10: 50 dBA |
|
Category 3 |
dBA: 50 dBC: 70 L10: 60 dBA |
dBA: 45 dBC: 65 L10: 55 dBA |
|
Category 4 |
dBA: 55 dBC: 75 L10: 65 dBA |
dBA: 50 dBC: 70 L10: 60 dBA |
This feature is verified by performance test, with the room unoccupied or at its lowest occupancy, ventilation running normally, sound masking switched off, and windows and doors closed.
S03 requires walls and doors that keep sound, especially speech, from carrying between enclosed rooms. It has two parts, one based on design and one on measured performance.
Part 1: Design for Sound Isolation at Walls and Doors (1 point). Interior walls must meet a minimum sound transmission class (STC) or weighted sound reduction index (Rw), both lab-tested ratings of how well a wall blocks sound, based on what types of spaces it separates. (Note: Projects that install sound masking under S06 Part 1 can use lower targets for most wall types.)
|
Wall separates |
Minimum STC/Rw |
With S06 Part 1 |
|
Loud zones and regularly occupied spaces |
60 |
60 |
|
Conferencing, learning, or sleeping areas and other occupied spaces |
55 |
50 |
|
Adjacent quiet zones |
50 |
45 |
|
Rooms for concentration and other occupied spaces |
45 |
40 |
|
Circulation zones and occupied spaces |
40 |
35 |
Doors between occupied rooms and doors to mechanical rooms must also have a non-hollow core, be rated at least STC/Rw 30, and be sealed at the head, jamb, and base. This part is verified by technical document.
Part 2: Achieve Sound Isolation at Walls (2 points). Walls between regularly occupied spaces are tested on site using one of two options:
S04 limits how long sound lingers in a room after its source stops, measured as RT60 (the time it takes sound to fade by 60 decibels). Its goal is reverberation times that support speech intelligibility and comfortable vocal effort and are conducive to concentration. The feature applies when the listed room types make up at least 10% of a project's occupiable area.
|
Room type |
Maximum reverberation time, by room volume (ft³) |
|
Learning, lecture, and conferencing areas |
0.6 s under 10,000 ft³ 0.8 s from 10,000 to 20,000 ft³ 1.0 s above 20,000 ft³ |
|
Areas with regularly used PA systems |
1.5 s |
|
Dining areas |
1.0 s |
|
Fitness areas |
0.8 s under 10,000 ft³ 1.1 s from 10,000 to 20,000 ft³ 1.8 s above 20,000 ft³ |
|
Music rehearsal areas |
1.1 s under 10,000 ft³ 1.4 s from 10,000 to 20,000 ft³ |
Rooms with more than one use follow the stricter limit. Projects can show compliance through design (verified by technical document) or by on-site testing (verified by performance test and technical document).
S05 requires sound-absorbing materials on ceilings, walls, and workstation partitions to reduce the buildup of speech and other noise. Materials are rated by noise reduction coefficient (NRC) or Alpha-w, both on a scale of 0 to 1 that reflects how much sound a surface absorbs. Like S04, it applies when the listed room types make up at least 10% of occupiable area.
|
Room type |
Tier 1 (1 point) |
Tier 2 (2 points) |
|
Open workspaces |
NRC 0.75 on at least 75% of the ceiling |
NRC 0.90 on the full ceiling, plus partitions at least 4 ft high with NRC 0.70 between all facing workstations |
|
Conferencing and learning areas |
NRC 0.75 on at least 50% of the ceiling and 25% of one wall |
NRC 0.90 on the full ceiling and NRC 0.80 on at least 25% of two perpendicular walls |
|
Dining areas |
NRC 0.75 on at least 50% of the ceiling |
NRC 0.90 on the full ceiling |
Ceiling coverage is measured against available ceiling area. This feature is verified by technical document.
S06 uses dedicated artificial sound, known as sound masking, to raise the background sound to a consistent, steady level. The IWBI notes that this shifts the balance between speech and background sound in favor of acoustical privacy, increasing speech privacy within and between occupied spaces.
Part 1: Provide Minimum Background Sound (1 point). In office spaces, a sound masking system must cover open areas, circulation zones, areas with workstations, and enclosed quiet rooms. It must:
This part is verified by technical document.
Part 2: Provide Enhanced Speech Reduction (1 point). Projects earn this point by combining S06 Part 1 with two points from either S03 Part 2 (measured wall isolation) or S05 (sound-absorbing surfaces).
S07 reduces impact noise, such as footfall, exercise, or equipment vibration, that travels through floor-ceiling assemblies, by designing resilient floors.
Both parts also require the beta feedback form, and neither applies to assemblies next to non-occupiable spaces such as roofs or equipment rooms.
S08 improves speech intelligibility through dedicated, high-performance audio technology and supports individual acoustical needs through organizational policies.
Part 1: Provide Enhanced Speech Intelligibility (1 point). As applicable to the project:
This part is verified by technical document.
Part 2: Prioritize Audio Devices and Policies (1 point). The organization must meet at least three of the following:
This part is verified by policy.
S09 is aimed at employees who are at risk of occupational hearing loss, such as staff in industrial settings or airports. To earn the point, the project maintains both of the following:
Both are verified by policy, plus the beta feedback form.
The WELL v2 Sound concept lists five verification pathways that projects can use to show that each requirement has been met:
Not directly, as the WELL v2 Sound concept is written today, but projects can apply for an Alternative Adherence Path (AAP) to use sensor data from continuous sound monitors.
Sound isn’t currently among the parameters that can be verified through the sensor data pathway, so features that require performance data can only be verified through an on-site performance test (for example, using a Class 1 sound level meter for feature S02 to measure background noise levels while the space is unoccupied or at its lowest occupancy).
An AAP is an alternative strategy, backed by evidence, that a project submits for approval to show it fully achieves a feature’s intent through a different method. For sound, that means demonstrating that data from continuous monitors fully meets the intent of each feature, such as showing that background noise levels stay within S02’s thresholds. Kaiterra is actively working with customers who are pursuing AAPs using continuous sound monitoring, and we have WELL APs and WELL faculty on staff who can help you navigate the process.
Using sensor data for sound is worth pursuing through an AAP, because continuous data brings benefits of its own. You can see how each space actually sounds day to day as factors like occupancy, HVAC cycles, and equipment use change. Continuous data is key to identifying where acoustic comfort isn't being achieved and confirming whether changes, such as new sound-absorbing surfaces or a sound masking system, keep working over time.
Whether you're working through the Sound concept for the first time or considering an AAP for continuous sound monitoring, reach out to a WELL AP on our team. We can help you map out which features fit your project and how sound data can support your IEQ goals and improve the occupant experience.