If you’re here because you’ve got questions about the ‘coverage area’ of your air quality monitors, how many monitors you need on your premises, or where to install them, then you’ve come to the right place. In this article, we’ll look at ‘coverage areas’, monitor density, and offer some guidance on how to get the most accurate readings from your IAQ monitors.
We get a lot of questions about the ‘coverage areas’ of IAQ monitors. The first thing you should know is that, in one sense, there is no such thing. Think of a thermostat. It can give you a fairly accurate reading of the temperature in the room, but it only measures the temperature of the air that directly comes in contact with it. If the thermostat is in the hallway, but the bedroom is freezing, the device has no way of picking up this information.
IAQ monitors work exactly the same way. They can only measure the quality of air that they come in contact with. They are effective because the air that they sample is roughly representative of the air nearby. This is because gasses naturally distribute themselves throughout a space, although some are denser at different heights. Air also tends to circulate in response to ventilation, heat, or movement, so that your IAQ monitor is usually measuring a different sample at any given time.
The problem is that air can’t easily bypass physical barriers, so your monitor will better represent the air six yards in front of it than six inches behind it, on the other side of the wall. Other factors like window drafts can also affect accuracy. For these reasons, instead of ‘coverage’, we prefer to talk about monitor density and placement guidelines based on established standards, such as the WELL performance rating and RESET Air.
Monitor density simply means the amount of monitors in a given space. The more IAQ monitors strategically placed in a premises, the better the picture given by their combined readings. Various organizations have issued guidelines about monitor density. Those issued by verified building standards institutes carry extra weight because following them can help you get accredited. The following organizations have issued guidelines:
The Well v2 is a highly regarded and comprehensive building standard issued by the International WELL Building Institute (IWBI). This standard has ten focus areas that include air, light, thermal comfort, and sound, among others. To get accredited with the Well v2, you will need:
Read more about achieving WELL through IAQ optimizations.
The RESET Air building standard is specifically designed to reward and promote the use of IAQ monitors for improving the health and wellbeing of occupants. This standard is unique in that it emphasizes continuous monitoring, and you can lose certification if monitoring stops while business continues. Meeting this standard requires that you:
Integrating IAQ sensors into your existing environment can be challenging if you're not familiar with what to look out for. The following considerations will help you take the best path to effectively mapping out your sensors:
Some gasses are heavier than others and you may find different concentrations at different heights. However, it’s most important to know what people will be taking into their lungs. For instance, airborne dust is usually densest near the floor, but not many people do their breathing at floor level. We recommend that our IAQ monitors are installed 3-6 feet (0.9-1.8 meters) from the floor. This height range is what we call the ‘breathing zone’, as it encompasses where a person’s head will typically be if they are sitting or standing.
A window draft may cause external air to circulate around one part of a room, while another part stagnates. It might only be in winter that you close your windows and realize that your air quality wasn’t half as good as you thought it was. Placement too close to air filters and diffusers can likewise cause IAQ monitors to read air that comes from outside a space, and not the space itself. To prevent this from happening, we recommend that you place monitors at least 16 feet (5 meters) from operable windows, air filters and diffusers. If this isn’t possible, the IAQ monitor should be at least half of the space away from a window, and closer to a return than a diffuser.
IAQ monitors are there to protect people, but large concentrations of staff release a lot of Co2 and can deplete oxygen levels in a poorly ventilated workspace, leading to reduced productivity and feelings of tiredness. For instance, a recent study showed that office workers worked up to 60% faster in low Co2 environments. If an IAQ monitor is too far from where people gather, it won’t register Co2 build-up or properly represent the air that they are breathing. For this reason, we suggest placing your IAQ monitors in central locations and prioritizing your most highly populated spaces.
Although neither thermostats, nor your IAQ monitor has what’s sometimes called a ‘coverage area’, there are many strategies to ensure they give you an accurate representation of the air in your workspaces. At Kaiterra, we advise against a one-size-fits-all approach, as each project and space is unique and will require a different strategy for monitor density. WELL and RESET guidelines are a good place to start, but consider them only a starting point. The best approach is to talk to a professional who can help you identify the proper density and placement of your monitors based on your project's details.
Need help mapping out your air quality monitors in your space? Our team is always happy to review your IAQ plan and provide our recommendations!